Finder 70.61.8.400.0000 Phase failure and sequence control relay for three-phase networks
Product Code: 28170618400
Quantity | Price | VAT excluded | VAT included |
---|---|---|---|
1 | Default | €62.472 | €76.21584 |
1 | Promo | €53.1012 | €64.783464 |
Finder 706184000000
Phase failure and sequence control relay for three-phase networks
Three-phase relay module for the detection of incorrect phase sequence, total or partial phase loss.
- Universal use (systems with UN 208 V to 480 V, 50/60 Hz)
- It detects phase failure error even in the presence of regenerated voltages
- Positive safety logic (the contact of the output relay opens in case of error detection)
- 1 switch, 6 A (width 17.5 mm)
- 35 mm rail mounting (EN 60715)
- European patent filed for the innovative principle underlying the 3-phase monitoring and error detection system
Mode of Operation
- If at the power supply the sequence (L1, L2, L3) is wrong, the relay will not close.
- If a phase is missing, the contact opens immediately.
- When it is activated again, the contact closes immediately.
- It detects the phase failure error even in the presence of regenerated voltages (up to 80% of the average of the remaining 2 phases).
More information is available in the product datasheet and for suggestions for the correct installation of the presence sensor we recommend that you consult the assembly instructions .
Product Codes: 70.61.8.400.0000, 706184000000, 8012823371993